Yueqing Osen Electrical Co.,Ltd.
Home | Favourites | Contact us | Chinese
HomeAbout usProductsCertificatesOnline orderDownloadContact usChinese
Product Seriesmore
Solar Products
MCB
RCCB, RCD,RCBO
MCCB
AC CONTACTOR
RELAY
FUSE
METER
SWITCH
CAPACITOR
POWER FACTOR REGULATOR
UPS STABLIZER
DISTRIBUTION BOX
PUSH BUTTON SWITCH
TRANSFORMER
INDUSTRIAL PLUGS & SOCKET
LIGHTING
TOOLS
ELECTRICAL ACCESSORY
Contact usmore
 
Product Introduction   
RCCD JVL1-100

Application scope
JVL1-63 II Residual Current Circuit Breaker provide the function of isolation switching and earth leakage protection of electrical circuits. And also provide the indirect protection of the operator's body against the dangerous effects of electric current and provide the protection of the fire caused by the electrical circuit fault.
Standard
IEC61008
Construction features 

1.Measuring component and buckling component of products is located between enter line end and entrance line end ;
2.Movement characteristic of products can not be changed with outside mechanical tool ;
3.The operating organization has the free function to take off and buckle;
4.Operate part can not be taken down from the shell outer of products , the shell can not influence the operating organization to work , the accessory group which replace the feelers pressure, should guarantee the feelers pressure does not change while running

Main technical parameters
Type
JVL1-63 II
Number of poles
2P4P
Rated Current(In)
25406380100A
Rated residual operating current( In)
1030100300500mA
Rated residual non-operation Current( Ino)
0.5In
Rated Voltage(Un)
AC 2P: 230/240V 4P: 400/415V
Residual operating current scope
0.5In~In
Residual current off-time
0.3s
Type
AAC
Ultimate short-circuit breaking capacity (Inc)
6000A
Endurance
4000
Terminal protection
IP20

Overall and mounting dimensioned chart 

CopyRight © Yueqing Osen Electrical Co.,Ltd